Daily Care and Maintenance of Centrifugal Pumps in Non-Negative Pressure Water Supply Equipment
Routine care and maintenance of centrifugal pumps is essential to their safe, reliable operation. Only when a centrifugal pump runs in good condition can it perform to its full potential and meet normal production needs.
Generally, centrifugal pumps are fully adjusted before leaving the factory. Within 6 months of purchase, an unused centrifugal pump does not need to be disassembled for inspection; simply check that it rotates freely, check for rust and add oil. For centrifugal pumps with packing seals, such as KKW series centrifugal pumps and horizontal multistage centrifugal pumps, packing must be added before use.
Routine care and maintenance of centrifugal pumps usually involves the following:
(1) Keep the equipment clean, dry, free of oil and free of leaks.
?
(2) Check daily that the pump sounds normal and has no vibration or leaks, and deal with any problems promptly.
(3) Check daily that the oil level in the bearing housing oil chamber is appropriate; it must be kept between 1/3 and 2/3 of the oil gauge.
(4) Never run the pump when the liquid in the tank (or drum) has been pumped dry. Running dry not only causes severe vibration but also shortens the pump's life, so special care must be taken.
(5) Do not allow metal objects or soft materials such as rubber, cotton yarn or plastic sheeting into the pump, to avoid damaging the wetted parts and blocking the impeller passages, which would stop the pump working normally.
(6) Check the alignment of the jaw coupling regularly.
(7) For pumps with packing seals, check the leakage at the stuffing box regularly; normal leakage is 10-20 drops per minute. Otherwise, adjust the tightness of the packing gland. Centrifugal pumps with mechanical seals, such as KKW series horizontal centrifugal pumps, are recommended.
(8) Check the bearing temperature frequently; the maximum should generally not exceed 70-75 °C.
(9) During the pump's first month of operation, replace the lubricating oil in the bearing housing after 100 hours; thereafter replace it every 500 operating hours.
(10) Frequently check that the supports of the pump's inlet and outlet piping (fittings and valves) are not loose. The supports must be secure so the pump body bears no support loads.
(11) Frequently check the tightness of the pump's foundation bolts to ensure a secure connection.
(12) If the pump will not be used for a long time, disassemble it, apply rust protection, reassemble it and store it properly for future use.
(13) When a standby centrifugal pump in the production system has not run for a long time, rotate it 1/4 turn every week so the shaft bears static loads and external vibration evenly.
(14) After about 2,000 hours of operation, carry out a periodic inspection and repair or replace damaged parts to keep the pump in good condition.
(15) For newly installed or overhauled pumps, always test the motor's direction of rotation before fitting the coupling pins.
(16) The pump may run in reverse when the motor loses power and liquid in the pipeline flows back. However, when the pump delivers over a very large height difference, a check valve should be installed on the pipeline to prevent backflow and sudden reverse rotation of the pump.
Back