What Chemical Tank Manufacturers Should Note During Inspection and Repair
1. Necessary fire-fighting equipment must be provided; smoking, open-flame lighting or heating, and bringing any ignition source into the tank area are strictly prohibited. 2. Before inspecting or repairing a tank, the power to all related electrical equipment must be cut off and equipment handover procedures completed. 3. After the tank has been fully drained, close the inlet and outlet valves or fit blind plates to isolate connected pipes and equipment, and post clear isolation signs. 4. Take samples for analysis 30 minutes before entering the tank; the oxygen content must be between 18% and 23% (by volume). 5. When entering the tank to clean out toxic or corrosive residues, wear proper personal protective equipment. 6. Lighting inside the tank must use explosion-proof lamps rated at no more than 24 V. 7. A standby attendant must be assigned for work inside the tank, with reliable means of communication. 8. On completion, maintenance staff and the attendant jointly inspect inside and outside the tank; only after confirmation and the attendant's signature on the confined-space work permit may the manholes be closed.