How Are GRP Shafts Made?
The GRP shaft is made of high-strength filament-wound GRP using a computer-controlled winding process to ensure uniform thickness that
meets design requirements. The base uses a grouted structure, and the station has a non-uniform diameter design, with the diameter at the bottom flow channel larger than that of the shaft body. GRP inner diameter ≥ 2.0 m, shaft thickness 20 mm and no less than the design requirement. A secondary grouting port is provided.
The integrated prefabricated pump station shaft must be verified by FEA (Finite Element Analysis), with a third-party FEA calculation report from a national institution or
university provided.
1) Warranty period: no less than two years. During the warranty period, products with quality problems will be replaced or refunded; after the warranty, lifelong maintenance and long-term technical sup
port are provided.
2) After-sales service: 24-hour on-call repair service, arriving on site within 4 hours of a fault report and resolving the fault within 4-8 hours (special peri
ods to be agreed separately).
3) In conjunction with equipment use and maintenance, free on-site training is provided to the buyer's management staff on basic equipment knowledge, operation and maintenance techniques,
ensuring the equipment stays in good condition after sale.
Basic pump control functions of integrated prefabricated pump stations
1) Duty rotation control: the pumps start and stop automatically and rotate duty based on the continuous level measured by the level transmitter (4-20 mA).
2) Redundant high-level control: a redundant hardware circuit design ensures that if the level transmitter fails, once the high-level float is triggered, the pumps start one after another
until the water reaches the low-level float, ensuring reliable operation of the whole station.
3) Scum clearing function: a built-in program eliminates scum on the station's water surface, with the number of daily clearing cycles adjustable.
4) Pump exercise control: when a pump has not run for a long time, the RTU should be able to start it briefly to ensure it continues to work normally.
Back