Process Description of Ion Deodorization Equipment
1. Process Description of Ion Deodorization Equipment
Each pump station in this project uses an energy-saving ion deodorization process, with no additional physical or chemical treatment facilities inside the equipment housing. The ion purification equipment produced by our company has the following main functional sections: fan section, oxygen ion generation section, waste gas deodorization treatment box section, and collection and exhaust system section.
1) Fresh-air filtration section
For deodorization efficiency and long-term operation of the purification equipment, impurities in the odorous gas must not enter the ion purification unit. A G4 or F5 grade filter is fitted at the air inlet before the ion generator, using filter media with high filtration efficiency, low pressure loss and small dimensions that can be removed, washed and reused. The pressure loss of this filter media is no more than 5 mmH2O, reducing the energy consumption and noise of the whole system.
2) Oxygen ion generation section
The oxygen ion generation section contains an oxygen ion generator, including high-grade quartz tubes made of advanced materials. To suit the deodorization process, ion output can be adjusted manually or automatically. To reduce duct resistance and save operating costs, the ion generator is installed horizontally. For the service life of the main equipment and the soundness of the whole process, the odorous gas does not come into direct contact with the ion generator, extending its service life. Under normal conditions, the wearing parts (ion tubes) of the ion generator last more than 20,000 hours of continuous operation, and the main unit lasts more than 15 years; ion output can be adjusted manually or automatically to suit the deodorization process.
The ion generation device uses a dedicated ion generator. The equipment and materials are suitable for long-term 24-hour continuous operation as well as intermittent operation. When the system is running normally, no dedicated staff are needed. Energy consumption is low, and installation and maintenance are simple and convenient. To reduce air resistance and installation size, the ion tubes on the generator are installed horizontally.
3) Waste gas deodorization treatment box section
Positive and negative ion gas mixes intensively and reacts with the polluted gas in the deodorization treatment box, decomposing and oxidizing pollutants and odors, thereby ensuring the purification efficiency of the whole deodorization system. To ensure stable year-round operation of the deodorization unit, there are no motorized equipment or electrical devices inside the treatment box.
4) Collection and exhaust system section
Based on the station's actual production process and the density of the polluted air, the form of enclosures and the height of exhaust inlets are chosen rationally, as close as possible to pollution sources or areas with higher concentrations of harmful substances. Airflow distribution, exhaust ducts and suitable exhaust fans (centrifugal), valves and fittings are arranged and selected according to the deodorization process requirements to remove harmful substances. To prevent harmful substances from accumulating locally and to maintain negative pressure indoors, the correct exhaust inlets, ducts and airflow are selected and set so that polluted indoor air pretreated with ionized air is displaced and fed into the waste gas deodorization treatment box.
For normal, stable operation of the whole deodorization system, the enclosed collection chamber is kept under negative pressure to prevent odors from escaping. Each ACE series ion deodorization unit uses 1 fan, installed at the end of the ion purification equipment. The fan is a side-suction centrifugal fan suitable for long-term 24-hour continuous operation in corrosive air. See the odor collection system description for details.
5) Electrical control system
Our company supplies a complete electrical control cabinet made of 304 stainless steel at least 2 mm thick, with an enclosure protection class of IP55. Electrical control of the ion-oxygen deodorization unit has both local and remote operating modes. In local mode, the equipment is started and stopped manually; when the control system is set to remote mode, the equipment can be started and stopped remotely, and status and alarm signals can be transmitted.
The electrical control box can provide the following signals to the station's PLC control system:
Run/stop signal (volt-free contact)
Normal/fault signal (volt-free contact)
Manual/auto status signal (volt-free contact)
Contact rating AC 250 V, 2 A
The electrical control box can receive start/stop commands from the PLC control system (contact rating AC 250 V, 2 A).
Electrical components use Schneider or equivalent-brand parts.
2. Performance Features:
A. Treated emission indicators: under normal operating and typical weather conditions, waste gas emission concentrations meet the following standards; odor concentrations at the site boundary meet the Class II boundary requirements of GB14554-93, and odor concentrations affecting surrounding receptors are below the limits for residential areas in the Hygienic Standards for the Design of Industrial Enterprises (TJ36-79):
B. Emission concentrations from the deodorization system meet the Class II emission standard of GB14554-93 in any season and under any weather conditions.
C. The system design complies with regulations. In the lower area of the pump room, an air supply system (waste gas pretreatment system) covers the surface of pollution sources with adjustable ionized gas, which reacts with the polluted gas to improve air quality in the area.
D. The system runs stably with strong resistance to shock loads, and an economical operating mode can be used while still meeting emission standards, reducing operating costs.
E. The system can run continuously or intermittently depending on operating conditions.
F. No mechanical, ventilation or other powered equipment may be installed in the box sections of the main deodorization equipment (ion generator) or the waste gas purification treatment box; noise does not exceed 60 dB(A). Ion generator: Type F.
G. In the ion purification units designed and manufactured by our company, the odorous gas in the equipment housing does not come into direct contact with the ion tubes, extending their life.
H. The equipment must not discharge at more than 6,000 V and must not produce ozone during operation.
I. Equipment maintenance or replacement of wearing parts and materials can be completed and the unit returned to normal service within 1 hour.
J. No other form of secondary pollution to the environment.
K. For long-term operation of the deodorization and purification equipment, a G4 or F5 grade filter is fitted at the air inlet before the ion generator.
L. Ion purification equipment features low energy consumption and high efficiency, and needs no dedicated maintenance staff under normal use. Daily operating costs consist of the electricity used by the fan and ion generator, calculated at industrial power rates.
Back